Technical / Programming Manual
FT128 Rev 2.2
117
Note: Enhanced Disablement is NOT valid when a time channel is used for disablements,
only when menu H2/B1-B2 are used.
14.15.1 Disable Zone
A whole zone (all addressable alarm points within a zone, including the manual call points)
can be disabled via menu H2/B1 or via the zone control front buttons (if fitted). This menu
is also used to disable a conventional zone, i.e. a 3361 unit's Zone Line Input (Z) and
expansion board 4580 Zone Line Inputs.
Re-enable via menu H2/B4 or automatic re-enabling at a specified time.
14.15.2 Disable Zone - Address
Individual alarm points can be disabled via menu H2/B2.
Re-enable via menu H2/B6 or automatic re-enabling at a specified time.
A time channel can instead be used to disable and re-enable automatically.
14.15.3 Disable Control Output
Individual control outputs can be disabled via menu H2/B3. Disabled output will stay in (or
return to) the normal condition for the output respectively until re-enabled.
Re-enable via menu H2/B7.
14.15.4 Disable all Control, Ventilation, Extinguishing or Interlocking Outputs
The control outputs of type "Control (general)", "Fire ventilation" and "Extinguishing system"
can be collectively disabled via menu H2/B4. Disabled outputs will stay in (or return to) the
normal condition for the output respectively until re-enabled via menu H2/B8.
14.15.5 Disable / Re-Enable Alarm Devices
The control outputs of type "Alarm device (OWS)" can be collectively disabled via menu
H2/B9. Disabled outputs will stay in (or return to) the normal condition for the output
respectively until re-enabled via menu H2/B9.
14.15.6 Disable / Re-enable Outputs for Routing Equipment
The control outputs of type "Routing equipment (Fire brigade TX and Fault TX)" can be
collectively disabled via menu H2/B10. Disabled outputs will stay in (or return to) the
normal condition for the output respectively until re-enabled via menu H2/B10.
14.15.7 Disable / Re-enable alert annunciation function
The alert annunciation function can be disabled via menu H2/B11. Disabled alert
annunciation function will be disabled until Re-enabled via menu H2/B11.
14.15.8 Disconnect / Re-Connect COM Loop
The COM loop can be disconnected via menu H8/S1. Disconnected COM loop will stay
disconnected until Re-connect via menu H8/S1.
14.15.9 Disconnect / Re-connect Zone Line Input
A Zone Line Input (e.g. on a 4580 board) can be disconnected via menu H8/S2.
Disconnected Zone Line Input will stay disconnected until Re-connect via menu H8/S2.