Technical / Programming Manual
FT128 Rev 2.2
140
Enhanced disablements: Disabled alarm point
will not activate pre-warning,
fire alarm or fault.
Checkbox not marked = Disabled alarm point
143
will not activate pre-warning or fire
alarm. Fault can still be activated.
This is a violation to the AS7240.2 standard.
Use special menu during fire alarm: Function, see FT128 Operation
Manual "Fire alarm menu (X1-X9)".
18.1.4.1 Door Closing By Time
Active: If all fire doors (trigger condition "Fire Door Closing") required to be closed
at a certain time every day, this checkbox is to be marked and the time (hh:mm)
set, e.g. 23:00.
18.1.4.2 Main Power Loss Fault Delay Time (Minutes)
A fault will be activated mm minutes after loss of mains power (230 V
AC
).
Default set at 30 minutes, allowable between 0-300 minutes.
The sensor values for a disabled analogue smoke detector will not be saved.