EasyManua.ls Logo

Brooks Firetracker FT128 CIE - 17 Control Unit Properties (Settings); Control Unit Properties Dialog Box; General Information; Configuration

Default Icon
182 pages
Print Icon
To Next Page IconTo Next Page
To Next Page IconTo Next Page
To Previous Page IconTo Previous Page
To Previous Page IconTo Previous Page
Loading...
Technical / Programming Manual
FT128 Rev 2.2
134
17 Control Unit Properties (Settings)
In EBLWin, please note:
EBL512 G3 = FT1020G3
EBL128 = FT128
Figure 43 The EBLWin "Control Unit Properties" Dialog Box.
Note: Default settings in EBLWin might vary depending on convention.
17.1 Control Unit Properties Dialog Box
Opens when you add a control unit or via the "Control unit" pop-up menu (Properties...)
17.1.1 General Information
Control unit number: An FT128 control unit has to have no. 0. No other number is allowed.
Name: Normally not changed but can be changed when required.
17.1.2 Configuration
Not valid for FT128.
MMI board (default)
Printer
17.1.3 Misc.
Configured number of alarm points: FT128 control unit can only have 256.
Suppress buzzer during fault from other control units: Not valid for FT128.
Use Pre-warning: This check box is to be marked if the pre-warning detection is required
to be enabled, i.e. pre-warnings will be activated. All programmable outputs in the system,
with trigger condition "Pre-warning", will be activated (if not disabled).

Table of Contents