Technical / Programming Manual
FT128 Rev 2.2
73
8 Input Programming
Input programming is performed in EBLWin. Each input must have an individual Trigger
condition "Type" and Logic. It is not allowed to let two or more inputs have the same trigger
condition for some inputs.
8.1 Type (Trigger Conditions)
The following trigger conditions are available:
1. Activated output
2. Activated fault routing equipment (one input)
3. Activated fire ventilation (one input)
4. Activated key cabinet (one input)
5. Activated Routing Equipment (one input)
6. Alarm Key Cabinet (one input)
7. Alert Annunciation Acknowledge
8. Alert Annunciation Reset
9. Door Closing Test Input
10. Evacuate (one input)
11. External Fault (up to 50)
12. External Time Channel (one input per time channel)
13. Extinguishing alarm
14. Extinguishing start
15. Extinguishing stop
16. Extinguishing system fault (one input)
17. Extinguishing system released (one input)
18. Fault Signal External Fuses (one input)
19. Fault Signal External Power Supply (one input)
20. Fault warning routing equipment fault (one input)
21. General Fire (maximum 100)
22. Interlocking (maximum 100)
23. Loss of battery charger to External Power Supply (one input)
24. Loss of main power source to external power supply (one input)
25. Not used
26. NZ Silence switch (one input)
27. Pre-warning
28. Technical warning (up to 100 per C.U.)
29. Zone Line Input
Only valid for the Addressable multipurpose I/O unit 3361 input "In0", used as Zone Line Input (Z).