Technical / Programming Manual
FT128 Rev 2.2
80
VO0-VO1 are set to outputs for "alarm device" by default.
24 V
DC
required from an external power supply unit (e.g. 3366AU).
Connections and more information see drawing F737.
9.7 The 4477 Unit Output (Siren)
Each unit has one programmable output:
Output Siren, with two priority levels and three sound types.
Connections and more information, see drawing F665 & F729.
9.8 The 3379 Unit Output (Sounder)
Each 3379 unit has one programmable output:
Output Sounder, with three priority levels and three sound types.
Also "High sound output" can be selected (4.5 dB).
Connections and more information, see drawing F665 & F729.
9.9 The 4380 unit output (beacon)
Each 4380 (under Obsolete Loop Units) unit has one programmable output:
Output Beacon
Connection is similar to other COM loop units as shown in drawing F729.
9.10 The 4383 unit output (Light indicator)
Each 4383 unit has one programmable output:
Output Light indicator
Connections and more information, see drawing F729.
The unit is discontinued and will be replaced with a new strobe approved to EN54.23.
4383 is discontinued, it is not complying with the new standard EN54.23 however the unit still can be used in the AU or NZ
markets until a compliant unit is released.