Technical / Programming Manual
FT128 Rev 2.2
180
29 Revision History
29.1 Revision History Table
Issue
Date
Description
Written By
Checked By
Panasonic
11/06/2010
Original Panasonic manual
J. Pattersson
A.S.
Rev 1
20/02/2012
Update the original MEW01351 Rev
1 document to suit AU & NZ market
A. Shenouda
E.T. / A.S.
Rev 1.1
30/05/2012
Update drawing F765 and F738,
update section 6.4 & 6.5
Edwin Thein
A.S.
Rev 2.2
12/08/2015
Update to include S/W V2.2.0 and
make minor corrections.
E.T. / A.S.
A.S.
29.2 Software Revision 2.2.0 Modifications
29.2.1 New common features and additions
Local Alarm Acknowledgement Unit 4445
The module is the Panasonic version of Brooks AAM, in EBLWin
the module is called “Local Alarm Acknowledgement Unit” LAAU.
Note: Brooks AAM (AAFC in EBLWin) has been moved to the
obsolete loop unit section in EBLWin.
Zone Groups
This is new control expressions that can be used to group unlimited number of
zones into one zone group. A single zone can be a member in only one zone group.
Maximum of 30 zone groups can be defined in a system. The new control
expressions for zone groups are as follow:
PreWarningZoneGroup (Zone Group, No. of alarms)
FireAlarmZoneGroup (Zone Group, No. of alarms)
HeavySmokeAlarmZoneGroup (Zone Group, No. of alarms)
FirstAlarmInZoneGroup (Zone, Zone Group)
Pulse on 3361 and 3364
The “Pulse” and “Delayed pulse” (defined in output signal period) can now be
programmed for the outputs of 3361 and 3364. The pulse width should be fixed for
7 seconds.
Selectable fire alarm types for Zone Line Inputs
In previous revisions, all fire alarms from a Zone Line Input via 3361 or 4580 are
treated as a normal fire alarm (type A). In V2.2.0, the Zone Line Input can be
programmed in EBLWin V2.2.0 to one of the following five different alarm types:
Smoke (B)
Heat (B)
MCP (A)
Other (A)
Other (B)