9.2 Control Unit Output R0
FT128 has one programmable relay output:
R0 Relay output, N/O or N/C contacts
80
programmable.
By default R0 is set to type "Routing equipment" (Fire brigade TX), Steady (cont.), normally
open and trigger condition "Fire brigade TX".
For connections and more information, see drawing F665.
9.3 8 Relay Outputs Expansion Board 4581 Output 0 Output 7
Each 4581 board has eight programmable relay outputs:
Output 0 Relay output, N/O or N/C contacts programmable
Output 1 Relay output, N/O or N/C contacts programmable
Output 2 Relay output, N/O or N/C contacts programmable
Output 3 Relay output, N/O or N/C contacts programmable
Output 4 Relay output, N/O or N/C contacts programmable
Output 5 Relay output, N/O or N/C contacts programmable
Output 6 Relay output, N/O or N/C contacts programmable
Output 7 Relay output, N/O or N/C contacts programmable
Relay contact ratings: Max. 2A @ 30 V
DC
.
For connections and more information, see dwg. F665.
9.4 Inputs and Outputs expansion board 4583 Output 01
Expansion board 4583 has two programmable, supervised
77
voltage outputs:
Output 0 Supervised voltage output, 24V
DC
78
, maximum 200 mA (Fuse F1).
Output 1 Supervised voltage output, 24V
DC
78
, maximum 200 mA (Fuse F2).
For connections and more information, see drawing F731.
See also chapter Inputs and Outputs Expansion Board 4583, page 26.
9.5 3361 Unit Outputs Re0 Re1
Each 3361 unit has two programmable relay outputs:
Re0 Relay output, N/O or N/C contacts programmable
Re1 Relay output, N/O or N/C contacts programmable
Relay contacts: maximum 2 A @ 30 V
DC
/ 125 V
AC
Connections and more information, see drawings F735.
9.6 3364 Unit Outputs VO0, VO1 & VO2
Each 3364 unit has two programmable, supervised voltage outputs
77
:
VO0 Supervised voltage output, 24V
DC
, maximum 1A
81
VO1 Supervised voltage output, 24V
DC
, maximum 1A
81
VO2 voltage output, 24V
DC
, max. 1A
81
, intended for fire door closing. Normally high.
80
Relay contacts: maximum 1 A @ 30 V
DC
.
81
Cont. 1 A, during 10 ms 1.4 A.