Loading...
Technical / Programming Manual
FT128 Rev 2.2
98
12.3.5 Re-enable Interlocking Output (H9/C5)
Interlocking outputs (i.e. Output Type = Interlocking) can be re-enabled via this menu
H9/C5.
Disabled interlocking outputs are listed in menu H9/C5. Use "↑" "↓" to scroll between the
"Interlocking Combinations" (i.e. Area / Point) or type it via the key-pad.
All the interlocking outputs, disabled via menu H2/B4, can be re-enabled collectively via
menu H2/B8.
12.4 Interlocking Control Expressions
A programmable output control expression can contain "interlocking" trigger conditions
("Functions") numbers 30-33 (see Section "Control Expression”, page 84 i.e. one or more
outputs can be activated when one or more interlocking inputs are activated.