Table 8
General electrical data
Descripon Rang Units
Supply voltage 3-phase Either 200 - 230 or 380 - 460 (see
rang plate)
V a.c.
Frequency 50/60 Hz
Wiring conguraon 3 wire plus Earth (ground)
Voltage tolerance range ± 10%
Installaon category II (IEC 60664-1)
Input supply voltage unbalance Should not exceed 2% when
assessed over any one minute
period
Short circuit current rang (when
installed with class T or class J fuses)
200 kA
Second protecve earth (ground)
conductor
Must be ed with cross‑seconal
area at least equal to phase
conductor size
Maximum permied overcurrent protecon for systems with the Han
®
K 4/4 mains
connector*
For 200 - 230 V systems
For 380 - 460 V systems
60
35
A
A
Typical earth leakage†
For 200 - 230 V systems
For GXS750/2600 and GXS750/4200
For all other GXS systems
9
<5
mA
mA
For 380 - 460 V systems:
For GXS750/2600 and GXS750/4200
For all other GXS systems
18
<10
mA
mA
* If the overcurrent protecon is used above the rangs in Table: Electrical data for the
systems with the Han®K 4/4, the minimum cable sizes no longer apply and you must
ensure that the pump cable size is appropriately rated and in accordance with local
legislaon and electrical regulaons. Ensure that the cable size is compable with the
mains connector. Refer to Table: Electrical connecons.
†Typical earth leakage values were measured at steady-state condions.
Note that higher leakage currents may occur:
i) under transient condions such as power on or pump acceleraon
ii) with the abnormal supply conguraons such as a missing or earthed phase or
unbalanced supply voltages.
Contact us for more informaon about the conguraon requirements for earth leakage
reducon.
Recommended fuse type:
Fuse Class gG (IEC 60269), UL class T, class J or class RK5, Bussmann type JJS or
equivalent 12t characterisc rated to 600 V.
Page 22
M58800880_H - Technical data