ECI Multi Functional Weighing Controller Operating Manual
Page 283
14.6.5 Setting the Relay 1 Minimum Value
Following data must be sent in order to set the minimum value of the 1. relay in Slot 4 as 500.
(Modbus ID:3 was used)
Modbus
ID
Function
Code
Start
Address
Register
Number
Byte
Number
Command
Register
Reg A Reg B CRC Data
03
10
00
00
00
03
06
00
80
00
00
01
F4
E0
0B
The response received is as follows.
Modbus
ID
Function
Code
Start
Address
Register
Number
CRC Data
03
10
00
00
00
03
81
EA