EasyManua.ls Logo

H3C UIS-Cell 3000 G3

H3C UIS-Cell 3000 G3
171 pages
To Next Page IconTo Next Page
To Next Page IconTo Next Page
To Previous Page IconTo Previous Page
To Previous Page IconTo Previous Page
Loading...
59
Figure 83 Installing the riser card
8. Connect PCIe module cables, if any.
9. Install the access panel. For more information, see "Installing the access panel."
10. Rack-mount the server. For more information, see "Rack-mounting the server."
11. Con
nect the power cord. For more information, see "Connecting the power cord."
12. Powe
r on the server. For more information, see "Powering on the server."
Installing storage controllers and power fail
safeguard modules
For some storage controllers, you can order a power fail safeguard module to prevent data loss
when power outage occurs.
A power fail safeguard module provides a flash card and a supercapacitor. When a system power
failure occurs, this supercapacitor can provide power for a minimum of 20 seconds. During this
interval, the storage controller transfers data from DDR memory to the flash card, where the data
remains indefinitely or until the controller retrieves the data.
Guidelines
For the storage controllers available for the server, see "Drive configurations."
Make sure the power fail safeguard module is compatible with the storage controller. For the
compatibility matrix, see "Storage controllers."
The supercapacitor might have a low charge after the power fail safeguard module is installed or
after the server is powered up. If the system displays that the supercapacitor has low charge, no
action is required. The system will charge the supercapacitor automatically.

Table of Contents

Related product manuals