13. Series 8 I/O Alarms and Failures
13.2. Reviewing IOM soft failures
270 Series 8 I/O User's Guide R500
Honeywell April 2017
When HALARMENABLE is disabled, all the existing HART events / alarms from that
channel block are disabled and further generation of the HART alarms / events are
terminated.
This parameter affects only the HART alarm / event behavior. The LED update of the
device status in the HART device status tab happens regardless of the state of
HALARMENABLE.
13.2 Reviewing IOM soft failures
IOM soft failures
The IOM reports device soft failures to Engineering station and also located on the
Control Builder configuration forms under the Soft Failures tab.
The table below lists all IOM soft failures and identifies those that appear within
Experion.
The SOFTFAIL1A, SOFTFAIL1B, SOFTFAIL2A, and SOFTFAIL2B parameters are
used to view an IOM's soft failures. For a list of channels in failure, use the
CHNLWFAILA and CHNLWFAILB parameters.
01 STCOVRUN
Sample time clock overrun.
Diagnostic check:
Investigate a possible I/O Link problem.
Cause:
Sample time clock overrun.
Solution:
Investigate a possible I/O Link problem or excessive IOL
activity. Check C300, IOL cables, IOMs, and IOL budgets. Call
TAC if the alarm persists or repeatedly occurs.

Table of Contents

Questions and Answers:

Question and Answer IconNeed help?

Do you have a question about the Honeywell Series 8 I/O and is the answer not in the manual?

Honeywell Series 8 I/O Specifications

General IconGeneral
BrandHoneywell
ModelSeries 8 I/O
CategoryI/O Systems
LanguageEnglish

Related product manuals