6. Series 8 I/O Configuration
6.6. Defining Channel blocks
R500 Series 8 I/O User's Guide 173
April 2017 Honeywell
Figure 50 Analog Output and Digital Output fault state (FAULTST)
transitions
Specific fault state handling depends upon the parameter settings for MODE and
MODEATTR. Refer to the tables below for Analog Output and Digital Output settings.
Table 42 Analog Output fault handling
Source
Destination
Mode
MODEATTR
FAULTSTATE
transitions
PID.OP
AO.OP
Cas
Operator or Program
1, 2, 3, 5, 7
PIDER.OP
AO.OP
Cas
Operator or Program
1, 2, 3, 5, 7
PID-PL.OP
AO.OP
Cas
Operator or Program
1, 2, 3, 5, 7
PIDFF.OP
AO.OP
Cas
Operator or Program
1, 2, 3, 5, 7
SCM
AO.OP
Man
Program
1, 2, 3, 5, 7
User
AO.OP
Man
Operator
1, 4, 6