13. Series 8 I/O Alarms and Failures
13.2. Reviewing IOM soft failures
286 Series 8 I/O User's Guide R500
Honeywell April 2017
181 FTAPOWFL
TC/RTD IOM is not able to power the FTAs.
TC/RTD IOM is not able to power the FTAs.
TC/RTD IOM is not able to power the FTAs.
Replace the IOM. This soft failure is introduced in Series 8.
182 DPADIAFAIL
IOL Address Diag Failure
IOL address diagnostic failure
IOL address diagnostic failure
Check IOM number at device index switch. Ensure correct
assignment. If not correct, reset to correct device index
number. Reset IOM.
183 RDBKRGDIAGFL
Readback Register Diagnostic Failure
Readback register diagnostic failure
Readback register diagnostic failure
Internal hardware problem. Replace the IOM.
184 WDTDIAGFAIL
Watch Dog Timer Diagnostic Failure
Watch Dog Timer diagnostic failure
Watch Dog Timer diagnostic failure