EasyManua.ls Logo

Honeywell Series 8 I/O - 7.10 DIMODE Related Scenarios; DIMODE Parameter Changes

Honeywell Series 8 I/O
293 pages
To Next Page IconTo Next Page
To Next Page IconTo Next Page
To Previous Page IconTo Previous Page
To Previous Page IconTo Previous Page
Loading...
7. Series 8 I/O Operations
7.10. DIMODE related scenarios
R500 Series 8 I/O User's Guide 223
April 2017 Honeywell
7.10 DIMODE related scenarios
DIMODE Parameter Changes
The following are examples of the DIMODE parameter when modified in different
views.
IOM
View
DIMODE
Description
DI24V,
DISOE
Project
Old value:
LowLatency
New value:
Normal
Configuration changes successfully
DI24V
Monitoring
Old value:
LowLatency
New value:
Normal
Throws an error "Invalid access
level "
DI24V
Monitoring
Old value:
Normal
New value:
LowLatency
Throws an error "Invalid access
level "
DISOE
Monitoring
Old value:
LowLatency/Normal/
Sequence of Events
New value:
LowLatency/Normal/
Sequence of Events
Throws an error "Invalid access
level "
DISOE
Project
Old value:
Sequence of Events
some channels have
EVTOPT = Sequence
of Events
New value:
LowLatency
Throws an error "DIMODE
incompatible with EVTOPT on one
or more channels"
Reload the CMs with channel block
after changing EVTOPT to NONE
on the channels with option
Sequence of Events.
Reload the IOM.
Configuration is loaded successfully
DISOE
Project
Old value:
Configuration changes
successfully.

Table of Contents

Related product manuals