5. Series 8 I/O Configuration Form Reference
5.18. Configuring HART Configuration tab - Channel block
R500 Series 8 I/O User's Guide 141
April 2017 Honeywell
5.18 Configuring HART Configuration tab - Channel block
Configuring modules - HART Configuration tab
The following configuration information pertains to the HART Configuration tab for all
Series 8 I/O Analog Input and Analog Output modules.
The parameter HALARMENABLE is added to HART configuration tab in the channel
block and:
is enabled by default
in addition, can be changed from monitoring side, irrespective of the channel point
execution state of the IOM module state.
ATTENTION
When HALARMENABLE is disabled
all the existing HART events / alarms from that channel block are
disabled
and further generation of the HART alarms / events are terminated
Note: This parameter affects only the HART alarm / event behavior. The LED
device status in the HART device status tab is not impacted by the state of
HALARMENABLE.
Prerequisites
Control Builder is running
A Series 8 I/O control module was created
Considerations
All illustrations used in the procedure are for example purposes only.
The following is an example of an Analog Input Channel Block, Configuration form -
HART Configuration tab.