TROUBLESHOOTING 
Part. No. 2400M2501_6    Touchpoint Pro 
  144  Technical Handbook 
Wait for the Inhibit Delay time to elapse. (If the Power-
On Delay or Fault Recovery Delay is enabled, the 
system will remain in Inhibit for a period defined by the 
Inhibit Delay Time.) Please refer to Ch. 9.3.13 Inhibit 
Delay Settings  
Sensor / 
Transmitter is 
signalling Inhibit 
The Sensor / Transmitter may be in a start-up 
sequence, or may have been inhibited for maintenance. 
Refer to the Input Details for that channel from the 
Inputs screen. 
There is a 
discrepancy 
between the 
sensor reading 
and the value 
displayed by 
Touchpoint Pro  
The mA loop 
requires 
calibration  
Touchpoint Pro converts the 4-20 mA signal it receives 
from the sensor to a gas reading. If the discrepancy is 
significant,  
re-calibrate the 4-20 mA loop by forcing the sensor 
output to 4 mA then 20 mA, see Commissioning, 
Calibrating a mA input channel 
Error ‘Calibration 
Signal Too High’ 
occurs when 
calibrating the mA 
loop 
The parameter 
‘Maximum Span 
Signal’ has been 
exceeded (default 
value 20 mA) 
Review the configuration of the channel. Under 
Calibration Settings, verify the value Maximum Span 
Signal. If necessary, use a lower forced mA value to 
calibrate the channel. Verify that the transmitter is 
operating correctly. 
HART 
communication 
with the 
corresponding 
field device 
HART communication with the field device may appear 
as a fluctuation on the incoming signal. This will clear 
when HART communication ceases. 
Verify that the system has a Bus Interface Board (BIB) 
fitted. Check the wiring between the Control Module 
terminal blocks TB6 and TB7 and the host computer 
system port. Try swapping over TDA and TDB. 
Check that the serial communication configuration 
parameters of the host computer system and 
Touchpoint Pro are the same. 
Ensure that the bus is correctly terminated. If this is the 
case remove the bus terminators and retry 
communication. 
Consider adding network bias resistors. Please refer to 
Ch. 11 Configuring Modbus for further details. 
Communication 
data errors 
Check the data signal wiring is not routed near sources 
of electrical noise. Check for earth loops. Ensure that 
the bus is correctly terminated. If this is the case remove 
the bus terminators and retry communication. 
Consider adding network bias resistors. 
If possible use an oscilloscope to examine the signals 
on the highway and take appropriate corrective action. 
No response from 
Touchpoint Pro 
Check the address parameter used in requests issued 
by the host computer system matches the address 
allocated to the slave node. In multi-drop systems check 
that all nodes have a unique address. 
Module is still 
showing as 
present and 
available for 
configuration in 
the System Setup 
Module has not 
been properly 
removed from the 
system 
Follow the instructions to remove a module from the 
system, see Maintenance, How to Remove or 
Decommission an I/O Module