201 Start Mode
This parameter determines the start function.
0 Start – normal start without interlockings
1 Interlocked Start – One of the inputs DI-2 to DI-6 must be programmed for
selection 13 or 14 “Interlock.” After start command, when the interlock is
removed the drive will stop and message “Interlock Missing” will be
displayed. When the interlock contact is closed the drive will start
automatically. NOTE: To do automatic start with interlock signal, the start
command must remain “ON”. Blinking “run” LED on the keypad will
indicate that “start” command is still on and the drive will start as soon
as the interlock contact is closed.
2 Interlock Time Start – This functions the same as the Interlocked Start,
except that if the interlock contact is not received within the Interlock
Timeout, an “IntlkTime Out” message is displayed and the start
sequence will need to be restarted.
3 Delay Start – This start is similar to the Interlocked Start, except that a
return contact is not used. After the “Delay Time” the Drive starts.
202 Interlock Timeout
The timeout time used for an Interlocked Time Start, after which the start sequence
must be restarted if no acknowledgement contact is received. See Start Mode (ID201).
203 Delay Time
The delay time following a Delay Start, after which the drive will be started. See Start
Mode (ID201).
204 DI-2 – DI6 function
This parameter has 17 selections.
0 Stop pulse, when 3-wire start/stop selected
1 External fault closed
2 External fault open
3 Fault reset
4 Run enable —
Contact open: Drive start disabled
Contact closed: Drive start enabled
5 Force ctrl. place to Hand
6 Force ctrl. place to Auto
7 Reverse
8 Speed Select 1
9 Fire Mode-Closed Contact
10 Speed Select 2
11 Speed Select 3
12 Force Bypass
13 Interlock – See parameter Start Mode ID201 for details, closed contact
14 Interlock – See parameter Start Mode ID201 for details, open contact
15 Motor potentiometer UP
16 Motor potentiometer DOWN
17 Fire Mode-Open Contact