EasyManua.ls Logo

Johnson Controls VSD Series - Figure 3-4; Table 3-4: Cable and Fuse Sizes - 525 - 690 V Ratings; Table 3-5: Maximum Symmetrical Supply Current; Table 3-6: Power Connection Tightening Torque

Johnson Controls VSD Series
252 pages
Print Icon
To Next Page IconTo Next Page
To Next Page IconTo Next Page
To Previous Page IconTo Previous Page
To Previous Page IconTo Previous Page
Loading...
Powered by Eaton Technology VSD Series Drives User Manual
LIT-1201828
For more information visit: www.johnsoncontrols.com 3-3
November 2009
Table 3-4: Cable and Fuse Sizes — 525 – 690V Ratings
If power cubes are used, a UL recognized RK fuse is recommended.
Based on maximum environment of 104°F (40°C).
If bypass is used, a UL recognized RK5 fuse is recommended.
Table 3-5: Maximum Symmetrical Supply Current
Table 3-6: Power Connection Tightening Torque
The isolation standoff of the bus bar will not withstand the listed tightening torque. Use a wrench to apply a counter torque when
tightening.
hp
Frame
Size
I
l
(A) Fuse (A)

Wire Size Terminal Size
Power Ground Power Ground
3
5
7-1/2
10
FR6
FR6
FR6
FR6
4.5
7.5
10
13.5
10
10
10
15
14
14
14
12
14
14
14
14
14 – 0
14 – 0
14 – 0
14 – 0
14 – 2
14 – 2
14 – 2
14 – 2
15
20
25
30
FR6
FR6
FR6
FR6
18
22
27
34
20
30
35
40
10
10
8
8
12
10
8
8
14 – 0
14 – 0
14 – 0
14 – 0
14 – 2
14 – 2
14 – 2
14 – 2
45
50
FR7
FR7
41
52
50
60
6
4
8
6
14 – 0
14 – 0
10 – 0
10 – 0
60
75
100
FR8
FR8
FR8
62
80
100
80
100
125
2
1
1/0
6
6
6
4 – 3/0
4 – 3/0
4 – 3/0
4 – 3/0
4 – 3/0
4 – 3/0
125
150
200
FR9
FR9
FR9
125
144
208
175
200
250
3/0
4/0
350
6
2
1/0
4 – 3/0
2x3/0 – 350 MCM
2x3/0 – 350 MCM
4 – 3/0
4 – 3/0
4 – 3/0
Product Voltage Maximum RMS Symmetrical Amperes on Supply Circuit
1 – 75 hp 230 100,000A
1-1/2 – 250 hp 480 100,000A
3 – 200 hp 575 100,000A
Rating Frame Size
Tightening Torque
(in-lbs)
Tightening Torque
(Nm)
230V, 1 – 3 hp
480V, 1-1/2 – 7-1/2 hp
FR4 5 0.6
230V, 5 – 10 hp
480V, 10 – 20 hp
FR5 13 1.5
230V, 15 – 20 hp
480V, 25 – 40 hp
575V, 3 – 30 hp
FR6 35 4
230V, 25 – 40 hp
480V, 50 – 75 hp
575V, 40 – 50 hp
FR7 88 10
230, 50 – 75 hp
480V, 100 hp
FR8 170/80
20/9
480V, 125 – 150 hp
575V, 60 – 100 hp
FR8 354/195
40/22
230V, 100 hp
480V, 200 – 250 hp
575V, 125 – 200 hp
FR9 354/195
40/22

Table of Contents

Other manuals for Johnson Controls VSD Series