EasyManua.ls Logo

Johnson Controls VSD Series - Figure 5-3: VSD Series Intellipass with Three Contactors

Johnson Controls VSD Series
252 pages
Print Icon
To Next Page IconTo Next Page
To Next Page IconTo Next Page
To Previous Page IconTo Previous Page
To Previous Page IconTo Previous Page
Loading...
Powered by Eaton Technology VSD Series Drives User Manual
LIT-1201828
For more information visit: www.johnsoncontrols.com 5-7
November 2009
Table 5-6: Bypass Power Wiring Instructions — NEMA Type 1 IntelliPass/IntelliDisconnect Drive (Continued)
Setting Overload
20. Lift to open the cover on the motor overload, and use a
1/8" flat-blade screwdriver to set the overload amperage to
match the value on the motor nameplate.
21. Turn the auto/manual reset (factory default is manual) on
the motor overload 90° to the auto position.
Control Wiring
22. Use a flat-blade screwdriver to carefully remove the low-
voltage I/O terminal block.
23. Insert the incoming control leads into the terminal block.
Refer to the electrical schematic supplied with the drive.
24. Reinsert the I/O terminal block into the control board.
25. Verify that all other wires to the terminal block are
connected.
26. Terminate control wiring to the OPTA9 and OPTA2 board
(Terminals 1 – 26).
Run 110 Vac and 24 Vdc control wiring in separate
conduit.
Communication wire must be shielded.
RS-232 keypad cable must be less then 25 feet.
Figure 5-3: VSD Series IntelliPass with Three Contactors
Auto/Manual
Reset
CONTROL WIRING
Drive
Ground
Motor
Ground
Note: Optional COMM cards can be supplied
Note: with the drive or as a field option.
Customer
Ground
Drive
Ground
Speed Select 1
Fire Mode
Bypass Overload Fault
Start/Stop
Note: See Figure 3
for Dip X1, X2,
X3, X6 Switch
settings.
OptionalOptional

Table of Contents

Other manuals for Johnson Controls VSD Series

Related product manuals