VSD Series Drives User Manual Powered by Eaton Technology
6-14 For more information visit: www.johnsoncontrols.com LIT-1201828
November 2009
Keypad Settings (S5.6)
There are five parameters (Default Page to Backlight Time) associated with the keypad
operation:
P5.5.3
Start-Up
Wizard
Range: Yes, No Default: No
Start-up Wizard
The Start-Up Wizard facilitates commissioning the drive. If selected active, the Start-
Up Wizard prompts the operator for the language and application desired and then
advances through the start-up parameter list. After completion it allows the user to
repeat the Start-Up Wizard or return to the default page, the Operate Menu. The
Start-Up Wizard in always active for the initial power up of the drive.
This feature can also be selected by pressing the STOP/RESET button for 5 seconds.
Display will then show “Start-Up Wizard Activated”. Unit must then be powered
down and “SUW” will be displayed on powerup.
Yes = Startup Wizard turns on every time power turns on.
P5.5.4
Multimonitor
Items
Range: ChangeEnable, ChangeDisabl Default: ChangeEnable
Multimon.items
The keypad display can display three actual monitored values at the same time. This
parameter determines if the operator is allowed to replace the values being
monitored with other values.
P5.6.1
Default Page
Range: 0 – 8 Default: 0
Default page
This parameter sets the view the display shows when entering the Programming
Mode. See Figure 6-3 on Page 6-5.
0,1 M1 Programming
2 M2 Keypad Control
3 M3 Active Faults
4 M4 Fault History
5 M5 System Menu
6 M6 Expander Boards
7 M7 Monitor
8 M8 Operate Mode
P5.6.2
Default Page
in the
Operating
Menu
Range: 0 – 16 Default: 0
Default page/OM
Here you can set the location in the Operating menu to which the display
automatically moves as the set Timeout Time expires, or when the keypad power is
switched on. See Table 6-14 on Page 6-21.
0,1 O1 Output Frequency
2 O2 Actual Speed
3 O3 Speed Setpoint
...
16 O16 Multimonitor
P5.6.3
Timeout Time
Range: 0 – 65,535
Units: Seconds
Default: 60
Timeout time
The Timeout Time setting defines the time after which the keypad display returns to
the Default Page.
Note: If the Default Page value is 0 the Timeout Time setting has no effect.

Table of Contents

Other manuals for Johnson Controls VSD Series

Questions and Answers:

Question and Answer IconNeed help?

Do you have a question about the Johnson Controls VSD Series and is the answer not in the manual?

Johnson Controls VSD Series Specifications

General IconGeneral
BrandJohnson Controls
ModelVSD Series
CategoryDC Drives
LanguageEnglish

Related product manuals