Checking the Cable and Motor Insulation
1. Check the motor cable insulation as follows:
Disconnect the motor cable from terminals U, V and W of the VSD Series drive and
from the motor.
Measure the insulation resistance of the motor cable between each phase conductor
as well as between each phase conductor and the protective ground conductor.
The insulation resistance must be >1MΩ.
2. Check the input power cable insulation as follows:
Disconnect the input power cable from terminals L1, L2 and L3 of the VSD Series
drive and from the utility line feeder.
Measure the insulation resistance of the input power cable between each phase
conductor as well as between each phase conductor and the protective ground
conductor.
The insulation resistance must be >1MΩ.
3. Check the motor insulation as follows:
Disconnect the motor cable from the motor and open any bridging connections in
the motor connection box.
Measure the insulation resistance of each motor winding. The measurement voltage
must equal at least the motor nominal voltage but not exceed 1000V.
The insulation resistance must be >1MΩ.

Table of Contents

Other manuals for Johnson Controls VSD Series

Questions and Answers:

Question and Answer IconNeed help?

Do you have a question about the Johnson Controls VSD Series and is the answer not in the manual?

Johnson Controls VSD Series Specifications

General IconGeneral
BrandJohnson Controls
ModelVSD Series
CategoryDC Drives
LanguageEnglish

Related product manuals