13 Configuration
192
Setup dialog – Counter/Int. 1 to 27 – Alarm
Parameter
Alarm rejection
If alarm rejection is active:
Incoming alarms are rejected (existing alarms become inactive) and
No entries are made in the alarm list and event list.
Parameter Selection/settings Description
Alarm type 1, 2 Inactive Monitoring is not active.
Min. alarm Alarm is issued if the limit value is not
met.
Max. alarm Alarm is issued if the limit value is
exceeded.
Limit value 1 -999999999 to 0.00000000 to
999999999
Limit value at which an alarm is issued.
Limit value 2 -999999999 to 100.000000 to
999999999
Limit value at which an alarm is issued.
Alarm text 1, 2 Use default text or enter other text. Text that is displayed or entered in the
status and title line and in the alarm list
and event list in the case of an alarm.
Alarm rejection Inactive
Digital selector
Signal (high active) for activating the
alarm rejection
Time delay 0s to 32767 s Delay time for alarm triggering
If the alarm is no longer on after the
delay time has elapsed, it is not trig-
gered.
?