Table 28: AC Power Cord Specifications (continued)
Plug TypeElectrical SpecificationModel NumberCountry
CEE (7) VII250 VAC, 10 A, 50 HzCBL-JX-PWR-EUEurope (except Italy and
United Kingdom)
CEI 23–16/VII250 VAC, 10 A, 50 HzCBL-JX-PWR-ITItaly
JIS 8303125 VAC, 12 A, 50 Hz or 60 HzCBL-JX-PWR-JPJapan
NEMA 5-15125 VAC, 10 A, 60 HzCBL-JX-PWR-USNorth America
BS 1363A250 VAC, 10 A, 50 HzCBL-JX-PWR-UKUnited Kingdom
WARNING: The AC power cord for the router is intended for use with the
router only and not for any other use.
WARNING: The attached power cable is only for this product. Do not use the
cable for another product. Translation in Japanese follows:
NOTE: In North America, AC power cords must not exceed approximately
14.75 ft (4.5 m) in length, to comply with National Electrical Code (NEC)
Sections 400-8 (NFPA 75, 5-2.2) and 210-52, and Canadian Electrical Code
(CEC) Section 4-010(3). You can order ACpower cordsthat are in compliance.
WARNING: The router is pluggable type A equipment installed in a
restricted-access location. It has a separate protective earthing terminal
(sized for SAE 10-32 ground screws) provided on the chassis in addition to
the grounding pin of the power supply cord. This separate protective earthing
terminal must be permanently connected to earth.
CAUTION: Power cords and cables must not block access to device
components or drape where people could trip on them.
57Copyright © 2017, Juniper Networks, Inc.
Chapter 8: AC Power Specifications and Requirements