S019
CAUTION:
The power-control button on the device does not turn off the electrical current supplied to the device.
The device also might have more than one connection to dc power. To remove all electrical current
from the device, ensure that all connections to dc power are disconnected at the dc power input
terminals.
Attention:
• Read
“Installation Guidelines” on page 57 and “Safety inspection checklist” on page 58 to ensure that you
work safely.
• Keep static-sensitive parts in their static-protective packages until installation to prevent exposure to
static electricity. Handle the parts with an electrostatic-discharge wrist strap or other grounding systems.
Place the parts on a static-protective surface.
Procedure
Step 1. If the server is in a rack, adjust the cable management arm (CMA) to gain access to the power
supply unit bay.
Figure 126. Adjusting the right side
a. Press down the stop bracket
1 and rotate it to the open position.
b. Rotate the CMA out of the way to gain access to the power supply units.
134
ThinkSystem SR630 V4 User Guide