Figure 188. The rear of CDU
Connect both drain and bleeder hoses to CDU.
Rotate the connectors to the right to secure the connection.
Important:
• For more operation and maintenance guidelines, see
Lenovo Neptune DWC RM100 in-rack
liquid Distribution Unit (CDU) Operation & Maintenance Guide
.
• For service support, associated warranty and maintenance sizing, contact Lenovo
Professional Services team at cdusupport@lenovo.com.
Step 11. Install the quick connect plug to the manifolds.
Figure 189. Installing the quick connect plug
a. Remove the rubber quick connect plug covers from the ports on the manifold.
b.
Connect the plug to the manifold port.
Step 12. Install the bleeder kit to the manifold supply side.
184 ThinkSystem SR630 V4 User Guide