EasyManua.ls Logo

Lenze 8400 StateLine C - Page 422

Lenze 8400 StateLine C
891 pages
To Next Page IconTo Next Page
To Next Page IconTo Next Page
To Previous Page IconTo Previous Page
To Previous Page IconTo Previous Page
Loading...
8400 StateLine C | Reference manual
Diagnostics & error management
Error messages of the operating system
422 L Firmware 11.00 - DMS 8.0 EN - 10/2011
dF21: BU watchdog [xx.0145.00033]
dF22: CU watchdog [xx.0145.00034]
dF10: AutoTrip reset [xx.0145.00035]
dF50: Retain error [xx.0145.00050]
dF51: CuCcr error [xx.0145.00051]
Ck16: Time overflow manual operation [xx.0184.00064]
Response (Lenze setting printed in bold)
0: No Reaction : 1: Fault 2: Trouble 3: TroubleQuickStop 4: WarningLocked 5: Warning 6: Information
Cause Remedy
Device error Consultation with Lenze required.
Response (Lenze setting printed in bold)
0: No Reaction : 1: Fault 2: Trouble 3: TroubleQuickStop 4: WarningLocked 5: Warning 6: Information
Cause Remedy
Device error Consultation with Lenze required.
Response (Lenze setting printed in bold) Setting: C00189 (; Adjustable response)
; 0: No Reaction : 1: Fault ; 2: Trouble ; 3: TroubleQuickStop ; 4: WarningLocked ; 5: Warning ; 6: Information
Cause Remedy
Too frequent auto-trip reset. Check the error cause that activates the auto-trip
reset.
Eliminate error cause and reset (acknowledge) error
manually afterwards.
Response (Lenze setting printed in bold)
0: No Reaction : 1: Fault 2: Trouble 3: TroubleQuickStop 4: WarningLocked 5: Warning 6: Information
Cause Remedy
An error has occurred when accessing retain data.
Either caused by an internal hardware error or by lack
of mains switching after a firmware download.
Mains switching
If the problem occurs again, you needs to consult
Lenze.
Response (Lenze setting printed in bold)
0: No Reaction : 1: Fault 2: Trouble 3: TroubleQuickStop 4: WarningLocked 5: Warning 6: Information
Cause Remedy
Device error Mains switching
If the problem occurs again, you needs to consult
Lenze.
Response (Lenze setting printed in bold)
0: No Reaction : 1: Fault 2: Trouble 3: TroubleQuickStop 4: WarningLocked 5: Warning 6: Information
Cause Remedy
Manual PC control: The connection monitoring has
tripped.
The online connection between the PC and the
controller has been interrupted for a longer period of
time than the timeout set in C00464/1
.
Check the communication link between the PC and
the controller.
Check the voltage supply/function of the controller.
Adjust the timeout (C00464/1
).
Phone: 800.894.0412 - Fax: 888.723.4773 - Web: www.clrwtr.com - Email: info@clrwtr.com