5.7 General function of the parameter setting
5.7.1 Parameterising digital I/Os
The parameter data of the digital I/O define if the control signals are to be transmitted with original
or inverted polarity.
For parameter data, 1 byte is available which is assigned via SDO.
Digital inputs are parameterised via the index I-6002.
Digital outputs are parameterised via the index I-6202.
The subindex depends on the slot.
[5-12] Display of the parameter date of digital I/Os
Tip!
Store changed parameters in the EEPROM via index I-1010. The settings are maintained
after the supply voltage is switched off.
Byte Assignment Lenze
0 Polarity of the transmitted
signals
Bit 0 0 Signal is transmitted 0x00
1 Signal is transmitted in
inverse form
Bit 1...7 Reserve