EasyManua.ls Logo

Lenze I/O system 1000 - Analog Inputs -10

Lenze I/O system 1000
583 pages
To Next Page IconTo Next Page
To Next Page IconTo Next Page
To Previous Page IconTo Previous Page
To Previous Page IconTo Previous Page
Loading...
9 PROFINET communication
9.6 Parameterising analog I/Os
485
Lenze · I/O system 1000 · Reference Manual · DMS 5.0 EN · 09/2016 · TD17
_ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _
9.6.5 2 analog inputs -10 ... +10 V (16 bits) - EPM-S406
Parameter data
During the execution time you can access the parameter data via the following data sets:
Data set Name Description/value Lenze
No. Byte
01Reserved 0
2 Limit value
monitoring
Bit 0: Channel 1 (0 = deactivated; 1 = activated)
Bit 1: Channel 2 (0 = deactivated; 1 = activated)
Bits 7 ... 2: reserved
0x00
1 0 Interference
frequency
suppression
Bit 1, 0: Channel 1
00: Deactivated
01: 60 Hz
10: 50 Hz
Bit 3, 2: Channel 2
00: Deactivated
01: 60 Hz
10: 50 Hz
Bit 7 ... 4: Reserved
0x00
128 0 Function channel 1 12 (0x12): -10 ... 10 V / -27648 ... 27648
34 (0x22): -10 ... 10 V / -16384 ... 16384
16 (0x10): 0 ... 10 V / 0 ... 27648
32 (0x20): 0 ... 10 V / 0 ... 16384
255 (0xFF): Channel deactivated
0x20
1 Reserved 0
2 Upper limit value
channel 1
Value from the rated range; if this value is exceeded and the
limit value monitoring function is active, a process alarm is
triggered.
0x7FFF: Limit value alarm deactivated
0x7FFF
3 Lower limit value
channel 1
Value from the rated range; if the actual value falls below
this value and the limit value monitoring function is active, a
process alarm is triggered.
0x8000: Limit value alarm deactivated
0x8000
129 0 Function channel 2 12 (0x12): -10 ... 10 V / -27648 ... 27648
34 (0x22): -10 ... 10 V / -16384 ... 16384
16 (0x10): 0 ... 10 V / 0 ... 27648
32 (0x20): 0 ... 10 V / 0 ... 16384
255 (0xFF): Channel deactivated
0x20
1 Reserved 0
2 Upper limit value
channel 2
Value from the rated range; if this value is exceeded and the
limit value monitoring function is active, a process alarm is
triggered.
0x7FFF: Limit value alarm deactivated
0x7FFF
3 Lower limit value
channel 2
Value from the rated range; if the actual value falls below
this value and the limit value monitoring function is active, a
process alarm is triggered.
0x8000: Limit value alarm deactivated
0x8000

Table of Contents

Related product manuals