5 CANopen communication
5.8 Parameterising analog I/Os
115
Lenze · I/O system 1000 · Reference Manual · DMS 5.0 EN · 09/2016 · TD17
_ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _
5.8.5 2 analog inputs -10 ... +10 V (16 bits) - EPM-S406
Parameter data
Index/subindex Name Description/value Lenze
I-3100/x Diagnostics Bit 0 ... 5: Reserved
Bit 6: Diagnostic alarm(0 = inhibited; 1 = enabled)
Bit 7: Reserved
0x00
I-3101/x Reserved 0
I-3102/x Limit value
monitoring
Bit 0: Channel 1 (0 = inhibited; 1 = enabled)
Bit 1: Channel 2 (0 = inhibited; 1 = enabled)
Bits 7 ... 2: reserved
0x00
I-3103/x Interference
frequency
suppression
Bit 1, 0: Channel 1
00: Deactivated
01: 60 Hz
10: 50 Hz
Bit 3, 2: Channel 2
00: Deactivated
01: 60 Hz
10: 50 Hz
Bit 7 ... 4: Reserved
0x00
I-3104/x Function channel 1 12 (0x12): -10 ... 10 V / -27648 ... 27648
34 (0x22): -10 ... 10 V / -16384 ... 16384
16 (0x10): 0 ... 10 V / 0 ... 27648
32 (0x20): 0 ... 10 V / 0 ... 16384
255 (0xFF): Channel deactivated
0x20
I-3105/x Reserved 0
I-3106/x
I-3107/x
Upper limit value
channel 1
Value from the rated range; if this value is exceeded and the
limit value monitoring function is enabled, a process alarm is
triggered.
0x7FFF: Limit value alarm deactivated
0x7FFF
I-3108/x
I-3109/x
Lower limit value
channel 1
Value from the rated range; if the actual value falls below
this value and the limit value monitoring function is enabled,
a process alarm is triggered.
0x8000: Limit value alarm deactivated
0x8000
I-310A/x Function channel 2 12 (0x12): -10 ... 10 V / -27648 ... 27648
34 (0x22): -10 ... 10 V / -16384 ... 16384
16 (0x10): 0 ... 10 V / 0 ... 27648
32 (0x20): 0 ... 10 V / 0 ... 16384
255 (0xFF): Channel deactivated
0x20
I-310B/x Reserved 0
I-310C/x
I-310D/x
Upper limit value
channel 2
Value from the rated range; if this value is exceeded and the
limit value monitoring function is enabled, a process alarm is
triggered.
0x7FFF: Limit value alarm deactivated
0x7FFF
I-310E/x
I-310F/x
Lower limit value
channel 2
Value from the rated range; if the actual value falls below
this value and the limit value monitoring function is enabled,
a process alarm is triggered.
0x8000: Limit value alarm deactivated
0x8000

Table of Contents