7 EtherCAT communication
7.12 Diagnostics
_ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _
7.12.5 Emergency telegram
Emergency messages are triggered by device-internal mechanisms and reported to the master by
the mailbox service of EtherCAT. If a state change cannot be executed for an EtherCAT gateway, it
is reported by a corresponding emergency message.
For a more detailed error description, the EtherCAT master reads out the AL status code (AL =
application layer). This is located in the EtherCAT coupler in the register ’0x0134’. Here you can find
the EtherCAT-specific error codes
( 401)
and Manufacturer-specific error codes
( 402)
.
Structure of the emergency message
The emergency messages are displayed as raw data in the »PLC Designer« and entered in the
logbook. Within this telegram, the reported error is entered as 5-digit hex value starting from the
"data:" information. The structure of the hex value corresponds to the bytes 3 ... 7 in the above table.
Example of an error message
07174 2013-06-04 10:12:04 _02M6D601 (1008): CoE emergency request.
id=0x0, len=8, ErrCode=0x0, ErrReg=0x8, data: 0x5 0x2 0x0 0x15 0x0.
Error information "data":
•Slot: 5
Type: Diagnostic alarm
Code: Error message ’0x0015’ (Invalid mailbox configuration)
Note!
Emergency frames can only be sent by modules that support alarm functions such as
"process alarm" or "diagnostic alarm". These are EPM-S404, EPM-S405, EPM-S406, EPM-
S408 and the counter modules EPM-S6xx.
The module-specific alarm structure is described in the following sections:
Process alarm data
( 384)
Diagnostic alarm data
( 386)
Bytes
0 1 2 3 4 5 6 7
Emergency Error
Lenze = 0xFF00
State
1: Init
2: Pre-Operational
3: Save-Operational
4: Operational
Data
Slot
Slot of the
error-
reporting
module.
Type
1: Process
alarm
2: Diagnostic
alarm
Code
Error code described for the
corresponding module.
Reserved
(any assignment)