5 CANopen communication
5.15 Loading the default setting
173
Lenze · I/O system 1000 · Reference Manual · DMS 5.0 EN · 09/2016 · TD17
_ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _
5.15 Loading the default setting
All parameter changes are reset to the default setting via index I-1011.
The default setting is accepted by switching the supply off and on again. Changes that you may have
carried out before will be deleted from the EEPROM of the I/O system.
Index Name Possible settings Info
Lenze Selection
I-1011 Restore All
Parameters
0 Resetting the parameter setting in
the EEPPROM of the bus coupler to
the Lenze setting.
Function in accordance with
CANopen (DS301/DS401
communication protocol).
0 Number of subindexes assigned Read only
Number of the subindices used by
the index I-1011
1Load 0 = no function
1684107116 = load Lenze setting
The numerical value is ASCII-coded
and complies with:
64 61 6F 0x6C = "D" "A" "O" "L"
After executing "Load", acceptance
is effected by
Voltage off/on, or
Transmission of a reset node
telegram (00 82 xx, with xx =
node address)