Lenze · I/O system 1000 · Reference Manual · DMS 5.0 EN · 09/2016 · TD17 472
9 PROFINET communication
9.3 Project planning
_ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _
9.3 Project planning
Project planning is carried out as hardware configuration in your PROFINET configuring tool as for
example the Siemens SIMATIC Manager. Here, you assign your I/O controller to the appropriate I/O
device. A direct assignment is made via the PROFINET address that can be set at the I/O device via
the address switch and the in I/O device properties.
By implementing the corresponding GSDML file, the PROFINET I/O bus coupler EPM-S140 is
specified under:
PROFINET IO -> More field devices -> I/O > I/O system 1000
GSDML file
Lenze provides you with a GSDML file for the I/O device. This file is either located on the enclosed
data medium or in the download area of www.lenze.de. Install the GSDML file in your configuring
tool. More information on how to install the GSDML file can be found in the manual of your
configuring tool.
For operating with your configuring tool, the GSDML file contains all I/O compound modules as XML
files.
After installing the GSDML file, you can find the I/O system 1000 in the hardware catalogue of
Siemens under:
PROFINET IO > More field devices > I/O > I/O system 1000
Commissioning
Set up your PROFINET system.
Start your configuring tool with a new project.
Configure a master system and create a new
PROFINET subnetwork.
For configuring the bus coupler, select the "EPM-S140" from the hardware catalogue and drag
it to the PROFINET subnetwork.
As soon as all switches of the address switch have the 0 status, the "DeviceName" can be
assigned freely via the properties of the PROFINET bus coupler. Otherwise assign a PROFINET
name via the switch position of the address switch.
If required, parameterise the I/O device.
Transfer your project into the PLC.