9 PROFINET communication
9.3 Project planning
473
Lenze · I/O system 1000 · Reference Manual · DMS 5.0 EN · 09/2016 · TD17
_ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _
Parameter data of PROFINET bus coupler
Diagnostic alarm type Here you can determine the structure of the diagnostic alarm data that are
sent via the diagnostic frame in the event of an error or be used to access standard PROFINET index
numbers.
Mnufacturer-specific data: You always obtain the data record DS 0x01 of the diagnostic data of a
module.
Channel-specific data: You always obtain the data record DS 0x00 of the diagnostic data of a
module.
Data format Motorola/Intel:This parameter refers to how a value is stored in the CPU address
range.
In the Motorola format (default), the bytes are stored in descending order, i.e. the first byte contains
the High byte and the second byte contains the Low byte.
In the Intel format, the bytes are stored in ascending order, i.e. the first byte contains the Low byte
and the second byte contains the High byte.
Parameter data of PROFINET bus coupler
Byte Bit 7 ... 0 Lenze
0 Bit 0: Process alarm
0 = inhibit
1 = enable
Bit 1: Diagnostic alarm
0 = inhibit
1 = enable
Bit 2: #Diagnostic alarm type
0 = manufacturer-specific data
1 = channel-specific data
Bit 3 ... 6: Reserved
Bit 7: Data format
0 = Data format Motorola
1 = Data format Intel
0x00
2 ... 6 0x00 (fix) 0x00