8 DeviceNet communication
8.3 Parameterising analog I/Os
_ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _
8.3.5 2 analog inputs -10 ... +10 V (16 bits) - EPM-S406
Parameter data
With the formulas listed in the following you can convert a digital value into an analog output value
and vice versa.
Position in
string
Name Description/value Lenze
No.
1 Diagnostics Bit 0 ... 5: Reserved
Bit 6: Diagnostic alarm(0 = inhibited; 1 = enabled)
Bit 7: Reserved
0x00
2 Reserved 0
3 Limit value
monitoring
Bit 0: Channel 1 (0 = deactivated; 1 = activated)
Bit 1: Channel 2 (0 = deactivated; 1 = activated)
Bits 7 ... 2: reserved
0x00
4 Interference
frequency
suppression
Bit 1, 0: Channel 1
00: Deactivated
01: 60 Hz
10: 50 Hz
Bit 3, 2: Channel 2
00: Deactivated
01: 60 Hz
10: 50 Hz
Bit 7 ... 4: Reserved
0x00
5 Function channel 1 12 (0x12): -10 ... 10 V / -27648 ... 27648
34 (0x22): -10 ... 10 V / -16384 ... 16384
16 (0x10): 0 ... 10 V / 0 ... 27648
32 (0x20): 0 ... 10 V / 0 ... 16384
255 (0xFF): Channel deactivated
0x20
6 Reserved 0
7 Upper limit value
channel 1
Value from the rated range; if this value is exceeded and the
limit value monitoring function is active, a process alarm is
triggered.
0x7FFF: Limit value alarm deactivated
0x7FFF
8 Lower limit value
channel 1
Value from the rated range; if the actual value falls below
this value and the limit value monitoring function is active, a
process alarm is triggered.
0x8000: Limit value alarm deactivated
0x8000
9 Function channel 2 12 (0x12): -10 ... 10 V / -27648 ... 27648
34 (0x22): -10 ... 10 V / -16384 ... 16384
16 (0x10): 0 ... 10 V / 0 ... 27648
32 (0x20): 0 ... 10 V / 0 ... 16384
255 (0xFF): Channel deactivated
0x20
10 Reserved 0
11 Upper limit value
channel 2
Value from the rated range; if this value is exceeded and the
limit value monitoring function is active, a process alarm is
triggered.
0x7FFF: Limit value alarm deactivated
0x7FFF
12 Lower limit value
channel 2
Value from the rated range; if the actual value falls below
this value and the limit value monitoring function is active, a
process alarm is triggered.
0x8000: Limit value alarm deactivated
0x8000