5 CANopen communication
5.18 Monitoring
_ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _
5.18.3 Monitoring of the analog outputs
Use index I-6443 to configure the response of the analog outputs if no telegram, node guarding
event, or heartbeat has been received within the defined monitoring time.
Monitoring is started if the next PDO telegram is received after the settings.
If a telegram is not transmitted within the time set, the modules switches to the Pre-
Operational state. Process data are not transmitted anymore.
A reset takes place by a change to Operational.
Individual response setting
Via index I-6444, the response can be individually configured for each analog output.
Index Name Possible settings Info
Lenze Selection
I-6443 Error mode analog
output
0 {1} 255 Configures analog output
monitoring
I-
6443
0
All analog outputs retain
the last value output
255
Response from I-6444
In I-6444, the response can be
configured individually for each
analog output
1 Channel 1 0
2 Channel 2 0
... ... ...
36 Channel 36 0
Index Name Possible settings Info
Lenze Selection
I-6444 Error value analog
output
-32768 {1} 32767 Configures the individual analog
output responses
The analog outputs provide the set
value
1 Channel 1 0
2 Channel 2 0
... ... ...
36 Channel 36 0