Lenze · I/O system 1000 · Reference Manual · DMS 5.0 EN · 09/2016 · TD17 32
2 Product description
2.7 PWM module EPM-S620 – control and status word
_ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _
2.7 PWM module EPM-S620 – control and status word
Status word EPM-S620
Control word EPM-S620
Bit Name Function
0– Reserved
1 PWM status 0: PWM output stopped
1: PWM output active
2 Output status 0: Push/Pull output
1: Highside output
3 ... 15 – Reserved
Bit Name Function
0 ... 1 – Reserved
2 PWM response • 0: Push/pull output
Push/pull mode should be used if you need defined high/low levels for a
rapid change. This is used with a low load especially if "highside" mode
cannot move the output to low fast enough during a low status. With
push/pull, the output is switched to ground with low active and to
voltage with high active.
•1: Highside output
In highside mode, the output switched to low remains in a state of
uncertainty between ground and voltage. The load has to "pull" itself to
ground. In highside mode, the switch is only made to high level active.
3 ... 7 Output status Reserved
8 Start PWM output 0-1-edge: PWM output is starting
9 Stop PWM output 0-1 edge: PWM output stops
10 ... 15 – Reserved