Lenze · I/O system 1000 · Reference Manual · DMS 5.0 EN · 09/2016 · TD17 156
5 CANopen communication
5.13 Parameterising technology modules
_ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _
5.13 Parameterising technology modules
5.13.1 2 digital outputs with PWM functionality - EPM-S620
Parameter data
Tip!
The pulse/pause ratio is determined by specifying the period (0x3100 ... 0x3107) and pulse
duration (0x5620).
Index/subindex Name Description/value Lenze
I-3100/x PWM 1:
Period byte 3
Set parameters here for the total time for pulse duration and
pulse pause. The time should be selected as a factor for the
20.83 ns basis.
Values below 25 s are ignored. If the pulse duration is
higher or equal to the period, the DO output is set
permanently.
Value range: 1200 ... 8388607 (25 s ... approx. 175 ms)
0x1F40
I-3101/x PWM 1:
Period byte 2
I-3102/x PWM 1:
Period byte 1
I-3103/x PWM 1:
Period byte 0
I-3104/x PWM 2:
Period byte 3
0x1F40
I-3105/x PWM 2:
Period byte 2
I-3106/x PWM 2:
Period byte 1
I-3107/x PWM 2:
Period byte 0
I-3108/x ...
I-3129/x
Reserved
I-5620/x PWM pulse duration Selection of pulse duration
Permissible values: 48 ... 8388607 (corresponds to 1 ...
175000 s