5 CANopen communication
5.9 Parameterising temperature measurement
135
Lenze · I/O system 1000 · Reference Manual · DMS 5.0 EN · 09/2016 · TD17
_ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _
5.9.3 Error behaviour
Index Name Possible settings Info
Lenze Selection
I-6443 Error mode analog
output
0 {1} 255 Configures analog output
monitoring
I-
6443
0
All analog outputs retain
the last value output
255
Response from I-6444
In I-6444, the response can be
configured individually for each
analog output
1 Channel 1 0
2 Channel 2 0
... ... ...
36 Channel 36 0
I-6444 Error value analog
output
-32768 {1} 32767 Configures the individual analog
output responses
The analog outputs provide the set
value
1 Channel 1 0
2 Channel 2 0
... ... ...
36 Channel 36 0