2 Product description
15 Lenze · I/O system 1000 · Reference Manual · DMS 5.0 EN · 09/2016 · TD17
_ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _
2 Product description
Features of the I/O system 1000
The I/O system 1000 is suitable for the implementation of complex automation applications
consisting of the following components: bus coupler module, I/O compound modules, and
backplane bus.
Modular system
•Dimensions
I/O compound module 109×76.5×12.5mm
Bus coupler module 109 × 76.5 × 48.5 mm
Mounting on standard DIN rail (35 mm)
Shield connection to standard metal rail (10 × 3 mm)
The two-piece structure (separation of electronics and process integration) enables a quick
exchange of modules in the event of service
Wiring level via spring terminal (max. 1.5 mm²)
Operation at DC 24 V (DC 20.4 DC 28.8 V)
Supply voltage of electronics and process level are separated
Number of I/O compound modules
A bus coupler can contain up to 64 modules
Individual labelling by insertable labels (item designation)
Electrical wiring diagrams are directly printed on the module
Electrical isolation to the fieldbus and the process level
Creation of electrical isolations by power supply modules