Lenze · I/O system 1000 · Reference Manual · DMS 5.0 EN · 09/2016 · TD17 402
7 EtherCAT communication
7.12 Diagnostics
_ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _
I: Init
P: Pre-Operational
S: Safe-Operational
O: Operational
B: Bootstrap
E: Error
7.12.7 Manufacturer-specific error codes
I: Init
P: Pre-Operational
S: Safe-Operational
O: Operational
B: Bootstrap
E: Error
0x0033 DC Sync IO Error O, S  OS + E
0x0034 DC Sync Timeout Error O, S  OS + E
0x0035 DC Invalid Sync Cycle Time P  SP + E
0x0036 DC Sync0 Cycle Time P  SP + E
0x0037 DC Sync1 Cycle Time P  SP + E
0x0041 MBX_AOE B, P, S, O Current state + E
0x0042 MBX_EOE B, P, S, O Current state + E
0x0043 MBX_COE B, P, S, O Current state + E
0x0044 MBX_FOE B, P, S, O Current state + E
0x0045 MBX_SOE B, P, S, O Current state + E
0x004F MBX_VOE B, P, S, O Current state + E
0x0050 EEPROM No Access Any Any + E
0x0051 EEPROM Error Any Any + E
0x0060 Coupler Restarted Locally Any I
< x8000 Reserved
Code Description Current State Resulting State
Code Description Current State Resulting State
0x8000 no module recognised or
present
II + E
0x8001 Module at system bus
needs update
P > S P + E
0x8002 Init error P > S P + E
0x8003 unexpected restart
(Watchdog)
P > S P + E
0x8004 Error reading EEPROM P > S P + E
0x8005 EPM-S130 module area too
big or small
P > S P + E

Table of Contents