EasyManua.ls Logo

Lenze I/O system 1000 - Setting the Cycle Time for Access to the I;O Modules

Lenze I/O system 1000
583 pages
To Next Page IconTo Next Page
To Next Page IconTo Next Page
To Previous Page IconTo Previous Page
To Previous Page IconTo Previous Page
Loading...
Lenze · I/O system 1000 · Reference Manual · DMS 5.0 EN · 09/2016 · TD17 72
4 Configuring the I/O system in the »PLC Designer«
4.3 Mapping the real station structure in the »PLC Designer«
_ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _
4.3.5 Setting the cycle time for access to the I/O modules
In the Lenze Controller a central bus cycle task is selected, which is valid for the processing of all
fieldbuses and for the I/O modules connected via the backplane bus.
This selection is a default setting and can be overwritten in the corresponding bus master nodes
(EtherCAT master, CANopen_Manager, I/O module coupler, ....).
If you require a shorter cycle time for the backplane bus than the one selected in the Lenze
Controller, you can select a faster task for I_O_Modul_Koppler on the Module I/O Mapping tab:
The following applies to I/O modules on the I_O_Modul_Koppler:
At first, the »PLC Designer« defines a processing task for the PLC for generating the I/O image.
An individual bus cycle task can be defined for each individual module, within which the process
image for the module is then created.
Altogether three different tasks for the I/O modules can be defined. The limitation to three
tasks is determined by the system on the basis of the backplane bus specification.
The backplane bus controller uses two internal bus cycle groups for each task; one for input
signals and one for the outputs. A total of six groups is provided.

Table of Contents

Related product manuals