Lenze · I/O system 1000 · Reference Manual · DMS 5.0 EN · 09/2016 · TD17 178
5 CANopen communication
5.18 Monitoring
_ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _
5.18 Monitoring
5.18.1 Time monitoring for PDO1-Rx ... PDO10-Rx
A time monitoring can be configured for the inputs of the process data objects PDO1-Rx ... PDO10-
Rx via index I-2400.
If no PDO is received within the time set in I-2400, the outputs will switch to their defined error
status (see following sections).
Index Name Possible settings Info
Lenze Selection
I-2400 Timer value 0
{1 ms}
65535 Monitoring time for process data
input objects
1Lenze-PDO Control
1
0
2Lenze-PDO Control
2
0
3Lenze-PDO Control
3
0
4Lenze-PDO Control
4
0
5Lenze-PDO Control
5
0
6Lenze-PDO Control
6
0
7Lenze-PDO Control
7
0
8Lenze-PDO Control
8
0
9Lenze-PDO Control
9
0
10 Lenze PDO control
10
0