6 PROFIBUS communication
6.4 Project planning
223
Lenze · I/O system 1000 · Reference Manual · DMS 5.0 EN · 09/2016 · TD17
_ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _
6.4 Project planning
The I/O system is configured via the master. The following work steps must be carried out:
Import the GSE file (device description) of the I/O system into the project planning tool.
PROFIBUS bus coupler: LENZ0C3A.gse
The description or linkage of the GSE file can be found in the project planning tool.
Address nodes
Every node at the PROFIBUS is identified by an address.
Each address may only be assigned once in a bus system.
Addresses between 1 ... 125 can be assigned.
At the PROFIBUS bus coupler (slave), the address with the front DIP switch is set
At the master, the address is set during the configuration.
Setting the baud rate
The baud rate is set in the configuration tool.
Adapt the baud rate to the length of the bus cable.
Parameterise slaves
Note!
The diagnostic function is only supported by I/O compound modules from HW version
1B and by bus coupler modules from HW version 1A.
If a module in the system complies with an earlier HW version, the diagnostic function
is deactivated for all modules.