Lenze · I/O system 1000 · Reference Manual · DMS 5.0 EN · 09/2016 · TD17 100
5 CANopen communication
5.4 Transmitting parameter data
_ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _
5.4 Transmitting parameter data
Parameter data are the indices.
The parameters are mostly set once during commissioning.
Parameter data are transmitted as SDOs (Service Data Objects) via the system bus and confirmed by
the receiver, i.e., the transmitter receives a feedback whether the transmission was successful.
5.4.1 Telegram structure
Structure of the telegram for parameter data:
The subchapters below explain the individual telegram components in detail.
Moreover, you will find examples of how to write and read a parameter
Writing a parameter (example)
( 103)
Reading a parameter (example)
( 105)
Identifier
One parameter channel is available for parameter data transmission, which is addressed via the
identifier.
11 Bit 8 bytes of user data
Identifier Command
code
Index Subindex Data 1 Data 2 Data 3 Data 4
Low byte High byte
Identifier = Basic identifier + node address of the device
dec hex
SDO Parameter channel 1
Output (transmit) 1408 580 + value set with coding switch
Input (receive) 1536 600