5 CANopen communication
5.3 Transmitting process data
99
Lenze · I/O system 1000 · Reference Manual · DMS 5.0 EN · 09/2016 · TD17
_ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _
I-1809/2 Transmission type
Defining the transmission mode.
Lenze setting: 255
0 Function deactivated The output data is accepted when the sync telegram
is transmitted.
1 ... 240 Process data transfer after
sync no. 1
...
Process data transfer
according to sync no. 240
The output data is accepted after the set number of
sync telegrams (1 ... 240) has been transmitted.
254 Time-controlled process data
transfer
Only if a cycle time is set in I-1809/5.
255 Event-controlled process
data transfer
Event-controlled process
data transfer with cyclic
overlay
Only if a cycle time is set in I-1809/5.
I-1809/3 0 ms 65535 Inhibit time
Lenze setting: 0 ms
I-1809/5 0 ms 65535 Event time (cycle time)
Lenze setting: 100 ms