Lenze · I/O system 1000 · Reference Manual · DMS 5.0 EN · 09/2016 · TD17 124
5 CANopen communication
5.9 Parameterising temperature measurement
_ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _
5.9 Parameterising temperature measurement
5.9.1 4(2) analog input for resistance measurement - EPM-S404
Parameter data
Note!
Use parameter setting to deactivate unused inputs.
If thermal detectors are connected in a 3 or 4 conductor setup, channels 3 and/or 4 must
be deactivated.
2-, 3-, 4-wire conductor measurement
( 26)
The module does not provide any auxiliary supply for sensors.
Index/subindex Name Description/value Lenze
I-3100/x Diagnostics A diagnostic alarm occurs if the same event triggers a further
process alarm during a process alarm processing.
Bit 0 ... 5: Reserved
Bit 6: Diagnostic alarm(0 = inhibited; 1 = enabled)
Bit 7: Reserved
0x00
I-3101/x Wire-breakage
detection
Bit 0: Channel 1 (0 = inhibited; 1 = enabled)
Bit 3: Channel 4
Bit 4 ... 7: Reserved
0x00
I-3102/x Limit value
monitoring
Bit 0: Channel 1 (0 = inhibited; 1 = enabled)
Bit 3: Channel 4
Bit 4 ... 7: Reserved
0x00
I-3103/x Reserved
I-3104/x Temperature system Bit 0, 1: 0b00 = °C; 0b01= °F; 0b10 = K
Bit 2 ... 7: Reserved
0x00
I-3105/x Interference
frequency
suppression
Bit 0, 1: 0b01 = 60 Hz; 0b10 = 50 Hz
Bit 2 ... 7: Reserved
0x02