7 EtherCAT communication
7.2 Transmitting process data
327
Lenze · I/O system 1000 · Reference Manual · DMS 5.0 EN · 09/2016 · TD17
_ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _
7.2.1 Access to the I/O area
SDO access can be used for read-only access to the object directory's input and output data.
Input data
When accessing the input area of an I/O compound module, addressing takes place via index I-6000
+ EtherCAT slot no. Subindices give you access to the corresponding input data. The relevant module
description contains the subindex assignment.
Output data
During read-only access to the output area of an I/O compound module, addressing takes place via
index I-7000 + EtherCAT slot no. Subindices give you read-only access to the corresponding output
data. The relevant module description contains the subindex assignment.
Index Subindex Name Type Attr. Default Meaning
I-6000
...
I-603F
0x00 Input data Unsigned8 ro Number of input data
subindexes for the
corresponding EtherCAT slot no.
0x01
0x02
...
ro
ro
Input data (see module
description)
Index Subindex Name Type Attr. Default Meaning
I-7000
...
I-703F
0x00 Output data Unsigned8 ro Number of output data
subindexes for the
corresponding EtherCAT slot no.
0x01
0x02
...
ro
ro
Output data (see module
description)