Lenze · I/O system 1000 · Reference Manual · DMS 5.0 EN · 09/2016 · TD17 134
5 CANopen communication
5.9 Parameterising temperature measurement
_ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _
Type C:
0 ... +2315 °C
32 ... 2786.5 °F
273.2 ... 2093.2 K
(0xB7: ext. comp. 0
°C)
(0xC7: int. comp. 0
°C)
+25000 32766 23432 Overflow
0 ... +23150 320 ... 27865 2732 ... 20932 Nominal range
-1200 -1840 1532 Underflow
Type E:
-270 ... +1000 °C
-454 ... 1832 °F
0 ... 1273.2 K
(0xB8: ext. comp. 0
°C)
(0xC8: int. comp. 0
°C)
+12000 21920 14732 Overflow
-2700 ... +10000 -4540 ... 18320 0 ... 12732 Nominal range
---Underflow
Type L:
-200 ... +900 °C
-328 ... 1652 °F
73.2 ... 1173.2 K
(0xB9: ext. comp. 0
°C)
(0xC9: int. comp. 0
°C)
+11500 21020 14232 Overflow
-2000 ... +9000 -3280 ... 16520 732 ... 11732 Nominal range
---Underflow
Measuring range Measured value Range
(Fct. no.) [°C] [°F] [K]