EasyManua.ls Logo

Lenze I/O system 1000 - Page 291

Lenze I/O system 1000
583 pages
To Next Page IconTo Next Page
To Next Page IconTo Next Page
To Previous Page IconTo Previous Page
To Previous Page IconTo Previous Page
Loading...
6 PROFIBUS communication
6.8 Parameterising the encoder evaluation
291
Lenze · I/O system 1000 · Reference Manual · DMS 5.0 EN · 09/2016 · TD17
_ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _
Diagnostic alarm processing
Using the SFB 52 you can read out the diagnostic bytes. If the diagnostic alarm is deactivated, you
can access the last diagnostic event in each case.
If you have activated the diagnostic function in your hardware configuration, OB 82 is called
automatically. Here you can react on the diagnostics accordingly. With the SFB 52 you can
additionally read out data set 1 which contains further information.
After exiting OB 82, the data can no longer be clearly assigned to the last diagnostic alarm.
Data set 1 is structured as follows:
Data set 1, diagnostic alarm
incoming
Byte Bit 7 ... 0
0 Bit 0: Set in the case of module fault
Bit 1: Set in the case of internal error
Bit 2: Set in the case of external error
Bit 3: Set if channel error available
Bit 4: Set in the case of missing external supply voltage
Bit 6 ... 5: 0 (fixed)
Bit 7: Parameterisation error
1 Bit 3 ... 0: Module class, 0b1000: Function module
Bit 4: Channel information available
Bit 7 ... 5: 0 (fix)
20 (fixed)
3 Bit 5 ... 0: 0 (fixed)
Bit 6: Process alarm lost
Bit 7: 0 (fixed)
4 Bit 6 ... 0: Channel type, 0x77: Counter module
Bit 7: 0 (fix)
5 Number of diagnostic bits output by the module per channel (here 0x08))
6 Number of channels of a module (here 0x01)
7 Bit 0: Error in channel group 0
8 ... 15 0 (fixed)
Data set 1, diagnostic alarm
outgoing
Byte Bit 7 ... 0
After the error correction, a diagnostic alarm
outgoing
takes place.

Table of Contents

Related product manuals